AC Contactor CJX1 Suppliers in China - High-Quality Factory Products for 50Hz/60Hz Circuits up to 660V
Type and meaning
Normal working conditions and installation conditions
Altitude: not higher than 2000m;
The ambient air temperature should be -5℃ ~+40℃, with the average temperature of no higher than +35℃ within 24 hours.
When the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature, such as not higher than 90% under +20℃. Special measures should be taken for occasional condensation due to temperature change;
Pollution level: level 3;
Installation category: category II;
Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°;
The product should be installed in a place without obvious shaking, impact and vibration.
Main parameters and technical performance
| Type | CJX1-9 | CJX1-12 | CJX1-16 | CJX1-22 | CJX1-32 | CJX1-45 | CJX1-63 | CJX1-75 | CJX1-85 | CJX1-110 | CJX1-140 | CJX1-170 | CJX1-205 | CJX1-250 | CJX1-300 | CJX1-400 | ||
| Rated insulation voltage U iv | 660 | |||||||||||||||||
| Rated working current le(A) | AC-3 | 380 | 9 | 12 | 16 | 22 | 32 | 45 | 63 | 75 | 85 | 110 | 140 | 170 | 205 | 250 | 300 | 400 |
| 660 | 7.2 | 9.5 | 13.5 | 13.5 | 18 | 45 | 63 | 75 | 75 | 110 | 110 | 170 | 170 | 200 | 250 | 320 | ||
| AC-4 | 380 | 3.3 | 4.3 | 7.7 | 8.5 | 12 | 24 | 28 | 4 | 42 | 54 | 68 | 75 | 96 | 110 | 125 | 150 | |
| 660 | 1.4 | 1.9 | 3.5 | 4 | 7.5 | 12 | 14 | 17 | 21 | 27 | 35 | 42 | 67 | 95 | 110 | 115 | ||
| Controllable power Pe(kW) | AC-3 | 380 | 4 | 5.5 | 7.5 | 11 | 15 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | 110 | 132 | 160 | 200 |
| 660 | 5.5 | 7.5 | 11 | 11 | 15 | 37 | 55 | 55 | 55 | 90 | 90 | 160 | 160 | 185 | 220 | 315 | ||
| AC-4 | 380 | 1.5 | 22 | 4 | 4 | 5.5 | 11 | 11 | 18.5 | 22 | 30 | 37 | 37 | 45 | 55 | 55 | 75 | |
| 660 | 11 | 15 | 3 | 4 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 55 | 75 | 90 | 110 | |||
| Conventional thermal current > It | A | 20 | 30 | 45 | 70 | 90 | 150 | 170 | 205 | 250 | 300 | 400 | ||||||
| Rated operating frequency times h | AC-3 | 1200 | 600 | 300 | ||||||||||||||
| AC-4 | 300 | 150 | ||||||||||||||||
| Mechanical endurance (10,000 times) | 1000 | 800 | 600 | |||||||||||||||
| Electrical endurance (10,000 times) AC-4 | AC-3 | 100 | 80 | 60 | ||||||||||||||
| 20 | 15 | 10 | ||||||||||||||||
| Specification of matched fuse(RT16)A | 16 | 20 | 25 | 32 | 50 80 | 100 125 | 160 | 200 | 200 | 250 | 250 | 300 | 400 | 500 | ||||
• The rated control power supply voltage Us of the contactor at AC 50/60 Hz is: 36/42, 48/58, 110/132, 127/152, 220/264, 380/456 (V).
• The contactor coil can reliably hold at 85%~110% of the rated control power supply voltage, and can reliably release at 20%~75% of the rated control power supply voltage.
• For the auxiliary circuit, the rated insulation voltage (Ui) is 660V; the conventional thermal current (Ith) is 10A; Other parameters are shown in the table below:
| Use category | Rated working voltage U e (V) | Rated working current I e (A) | Rated control power | |
| AC VA | DC W | |||
| AC-15 | 36 | 10 | 360 | |
| 110 | 3.2 | |||
| 220 | 1.64 | |||
| 380 | 0.95 | |||
| DC-13 | 48 | 0.69 | 33 | |
| 110 | 0.3 | |||
| 220 | 0.15 | |||
Outline and installation dimensions

Fig.1 Outline and installation dimensions of CJX1-9/32
| Type | a max | b | c max | d | e max | g | Φ |
| CJX1-9/12 | 79 | 60±0.60 | 46 | 35±0.50 | 106 | 8 | +0.48 4.8 |
| CJX1-16/22 | 89 | 75±0.60 | 46 | 35±0.50 | 116 | 8 | |
| CJX1-32 | 90 | 75±0.60 | 74 | 50±0.55 | 109 | 8 | .+0.48 |
Frequently Asked Questions (FAQ)
What are the standard ambient temperature limits for CJX1 AC contactors?
The ambient air temperature must be within the range of -5℃ to +40℃. Additionally, the average temperature over a 24-hour period should not exceed +35℃ to ensure normal operation.
What is the maximum installation altitude for these contactors?
The CJX1 series AC contactors are designed for installation in areas with an altitude not exceeding 2000 meters above sea level.
How does relative humidity affect the contactor's performance?
At a peak temperature of +40℃, relative humidity should not exceed 50%. However, higher humidity is acceptable at lower temperatures (e.g., up to 90% at +20℃). Precautionary steps should be taken to manage occasional condensation.
What are the coil holding and releasing voltage ranges?
The contactor coil is designed to reliably hold between 85% and 110% of its rated control power supply voltage. It will reliably release within 20% to 75% of the rated control power supply voltage.
What are the requirements for the installation angle?
The contactor should be installed on a surface where the inclination relative to the vertical plane does not exceed ±5°. The environment should also be free from significant vibration or shock.