AC Contactor CJX2 - High-Quality China Suppliers & Factory | 50Hz/60Hz, Up to 690V, 95A Rating
Type and meaning
Note 1:
09A-95A adopts the number of auxiliary contacts, while 115A-800A adopts the number of poles.
10 means three normally open main contacts and one normally open auxiliary contact (32A and below);
01 means three normally open main contacts and one normally closed auxiliary contact (32A and below);
11 means three normally open main contacts, one normally open auxiliary contact and one normally closed auxiliary contact (40A and above).
Normal working conditions and installation conditions
- The ambient air temperature should be -5℃~+40℃, with the average temperature of no higher than +35℃ within 24 hours.
- Altitude: not higher than 2000m;
- Atmospheric conditions: when the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature such as 90% under 20℃. Special measures should be taken for occasional condensation due to temperature change.
- Pollution level: level 3;
- Installation category: category III;
- Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°;
- Impact vibration: the product should be installed and used in a place without obvious shaking, impact and vibration.
Main parameters and technical performance
Main parameters and technical performance index contactor
| Type | CJX2-09 | CJX2-12 | CJX2-18 | CJX2-25 | CJX2-32 | CJX2-40 | CJX2-50 | CJX2-65 | CJX2-80 | CJX2-95 | ||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Rated working current | 400(380)V | AC-3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
| AC-4 | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | ||
| 690(660)V | AC-3 | 6.6 | 8.9 | 12 | 18 | 21 | 34 | 39 | 42 | 49 | 49 | |
| AC-4 | 1.5 | 2 | 3.8 | 4.4 | 7.5 | 9 | 12 | 14 | 17.3 | 21.3 | ||
| Conventional free air thermal current | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 95 | 95 | ||
| Rated insulation voltage | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | ||
| Controllable three-phase squirrel cage motor power (AC-3) kW | 230(220)V | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 | |
| 400(380)V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | ||
| 690(660)V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 37 | 37 | 45 | 45 | ||
| Operating frequency (times/h) | Electrical endurance, mechanical endurance | AC-3 | 1200 | 1200 | 1200 | 1200 | 600 | 600 | 600 | 600 | 600 | 600 |
| AC-4 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | ||
| 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | |||
| Electrical endurance (10,000 times) | AC-3 | 100 | 100 | 100 | 100 | 80 | 80 | 60 | 60 | 60 | 60 | |
| AC-4 | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 15 | 10 | 10 | ||
Outline and installation dimensions

Outline and installation dimensions of CJX2-09~32

Outline and installation dimensions of CJX2-40~95
| Contactor type | A max | B max | C max | D max | E max | a | b | φ |
|---|---|---|---|---|---|---|---|---|
| CJX2-09~12 | 47 | 76 | 82 | 120.5 | 140.5 | 34/35 | 56/60 | 4.5 |
| CJX2-18 | 47 | 76 | 87 | 125.5 | 145.5 | 34/35 | 50/60 | 4.5 |
| CJX2-25 | 57 | 86 | 95 | 133.5 | 153.5 | 40 | 48 | 4.5 |
| CJX2-32 | 57 | 86 | 100 | 138.5 | 158.5 | 40 | 48 | 4.5 |
| CJX2-4011~6511 | 77 | 129 | 116 | 154.5 | 174.5 | 40 | 105 | 6.5 |
| CJX2-4004~6504 | 84 | 129 | 116 | 154.5 | 174.5 | 40 | 105 | 6.5 |
| CJX2-40086~508 | 84 | 129 | 127 | 154.5 | 174.5 | 40 | 105 | 6.5 |
| CJX2-8011~9511 | 87 | 129 | 127 | 165.5 | 185.5 | 40 | 105 | 6.5 |
| CJX2-8004~9504 | 96 | 129 | 122 | 160.5 | 180.5 | 40 | 105 | 6.5 |
| CJX2-8008~9508 | 96 | 129 | 135 | 160.5 | 180.5 | 40 | 105 | 6.5 |
Frequently Asked Questions (FAQ)
Q1: What is the meaning of auxiliary contact codes 10, 01, and 11?
A1: For contactors 32A and below, "10" indicates three normally open main contacts and one normally open auxiliary contact; "01" indicates three normally open main contacts and one normally closed auxiliary contact. For contactors 40A and above, "11" indicates three normally open main contacts, one normally open auxiliary contact, and one normally closed auxiliary contact.
Q2: What are the normal ambient air temperature limits for CJX2 contactors?
A2: The ambient air temperature should be within the range of -5℃ to +40℃, and the average temperature over a 24-hour period must not exceed +35℃.
Q3: What is the maximum installation altitude and inclination allowed?
A3: The installation altitude must not be higher than 2000 meters. The inclination angle between the installation surface and the vertical plane must not exceed ±5°.
Q4: How do atmospheric conditions and humidity affect installation?
A4: At the maximum temperature of +40℃, relative humidity should not exceed 50%. Higher relative humidity, up to 90%, is acceptable at lower temperatures (such as under 20℃). Special measures must be taken to handle occasional condensation caused by temperature changes.
Q5: What are the insulation voltage and pollution level ratings for this series?
A5: The CJX2 series contactors have a rated insulation voltage of 690V, a pollution level rating of level 3, and fall under installation category III.
Q6: What is the rated electrical endurance of the CJX2-09 contactor under AC-3 conditions?
A6: Under AC-3 operating conditions, the CJX2-09 contactor has an electrical endurance rating of 100 x 10,000 times (1,000,000 operations).