AC Contactor ZNFO Transcender Series - China Suppliers and Factory for Reliable Motor Control and Circuit Protection

The ZHC series AC contactor is an essential component for electrical systems in China, designed for use in circuits operating at frequencies of 50Hz or 60Hz, with voltages reaching up to 690V and a rated working current of up to 95A. This product is ideal for applications categorized under AC-3 and 400(380)V, allowing for the reliable remote control and disconnection of circuits. It excels in frequently starting and controlling AC motors and can be combined with the appropriate thermal relay to create an electromagnetic starter, ensuring circuit protection against potential overloads. Manufactured by trusted suppliers in China, our factory adheres to the highest standards, including GB/T-14048.4-2020 and IEC60947-1 (1999), along with IEC 947-4-1, ensuring top quality and performance

    Advantage

    All products of the company can be customized for production according to user usage scenarios.

    Type and meaning

    dfgse
    Note l

    09A-95A adopts the number of auxiliary contacts, while 115A-800A adopts the number of poles.

    10 means three normally open main contacts and one normally open auxiliary contact (32A and below);

    01 means three normally open main contacts and one normally closed auxiliary contact (32A and below);

    11 means three normally open main contacts, one normally open auxiliary contact and one normally closed auxiliary contact (40A and above).

    Normal working conditions and installation conditions

    • The ambient air temperature should be -5℃ ~+40℃, with the average temperature of no higher than +35℃ within 24 hours.
    • Altitude: not higher than 2000m;
    • Atmospheric conditions: when the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature, such as 90% under 20℃. Special measures should be taken for occasional condensation due to temperature change;
    • Pollution level: level 3;
    • Installation category: category III;
    • Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°;
    • Impact vibration: the product should be installed and used in a place without obvious shaking, impact and vibration.

    Main parameters and technical performance

    Main parameters and technical performance indicators of the contactor
    Type ZHC-09 ZHC-12 ZHC-18 ZHC-25 ZHC-32 ZHC-40 ZHC-50 ZHC-65 ZHC-80 ZHC-95
    Rated working current 400(380)V AC-3 9 12 18 25 32 40 50 65 80 95
    AC-4 3.5 5 7.7 8.5 12 18.5 24 28 37 44
    690(660)V AC-3 6.6 8.9 12 18 21 34 39 42 49 49
    AC-4 1.5 2 3.8 4.4 7.5 9 12 14 17.3 21.3
    Conventional free air thermal current 20 20 32 40 50 60 80 80 95 95
    Rated insulation voltage 690 690 690 690 690 690 690 690 690 690
    Controllable three-phase squirrel cage motor power (AC-3) kW 230(220)V 2.2 3 4 5.5 7.5 11 15 18.5 22 25
    400(380)V 4 5.5 7.5 11 15 18.5 22 30 37 45
    690(660)V 5.5 7.5 10 15 18.5 30 37 37 45 45
    Operating frequency (times/h) Electrical endurance mechanical endurance AC-3 1200 1200 1200 1200 600 600 600 600 600 600
    AC-4 300 300 300 300 300 300 300 300 300 300
    3600 3600 3600 3600 3600 3600 3600 3600 3600 3600
    Electrical endurance (10,000 times) AC-3 100 100 100 100 80 80 60 60 60 60
    AC-4 20 20 20 20 20 15 15 15 10 10

    Outline and installation dimensions

    cdgern3
    Outline and installation dimensions of ZHC-09~32
    cdgern4
    Outline and installation dimensions of ZHC-40~95
    Contactor type A max B max C max D max E max a b φ
    ZHC-09~12 47 76 82 120.5 140.5 34/35 56/60 4.5
    ZHC-18 47 76 87 125.5 145.5 34/35 50/60 4.5
    ZHC-25 57 86 95 133.5 153.5 40 48 4.5
    ZHC-32 57 86 100 138.5 158.5 40 48 4.5
    ZHC-4011~6511 77 129 116 154.5 174.5 40 105 6.5
    ZHC-4004~6504 84 129 116 154.5 174.5 40 105 6.5
    ZHC-4008~6508 84 129 127 154.5 174.5 40 105 6.5
    ZHC-8011~9511 87 129 127 165.5 185.5 40 105 6.5
    ZHC-8004~9504 96 129 122 160.5 180.5 40 105 6.5
    ZHC-8008~9508 96 129 135 160.5 180.5 40 105 6.5

    Frequently Asked Questions

    Can these products be customized for specific applications?

    Yes, all products of the company can be customized for production according to user usage scenarios.

    What do the auxiliary contact numbers 10, 01, and 11 mean?

    "10" means three normally open main contacts and one normally open auxiliary contact (32A and below); "01" means three normally open main contacts and one normally closed auxiliary contact (32A and below); "11" means three normally open main contacts, one normally open auxiliary contact, and one normally closed auxiliary contact (40A and above).

    What are the ambient temperature requirements for installation?

    The ambient air temperature should be between -5℃ and +40℃, with an average temperature of no higher than +35℃ within a 24-hour period.

    What is the maximum installation altitude for these contactors?

    The installation altitude should not exceed 2000 meters above sea level.

    How does humidity affect the operating conditions?

    At the maximum temperature of +40℃, relative humidity should not exceed 50%. However, higher relative humidity is allowed at lower temperatures (e.g., 90% under 20℃). Special measures should be taken for occasional condensation due to temperature changes.

    What is the permitted inclination angle for mounting the device?

    The inclination between the installation surface and the vertical plane should not exceed ±5°.