China AC Contactor ZNFO Green Innovation Series - 95A Electric Motor Control Suppliers & Factory

The ZHCt modified AC contactor is an essential component for electrical circuits operating at frequencies of 50Hz or 60Hz. With a voltage capacity of up to 690V and a rated working current up to 95A, this contactor is designed for use in AC-3 and 400(380)V categories. It efficiently connects and disconnects circuits remotely, frequently starts, and controls AC motors. When paired with a suitable thermal relay, it forms an electromagnetic starter that effectively protects circuits against potential overloads. Manufactured in China, our contactors adhere to international quality standards, including GB/T14048.4-2020 and IEC60947-1(1999). As a leading supplier and factory, we ensure high-quality products that meet diverse industrial needs

    Advantage

    All products of the company can be customized for production according to user usage scenarios.

    Type and meaning

    dfhgrt
    Note l:
    09A-95A adopts the number of auxiliary contacts, while 115A-800A adopts the number of poles.
    11 means three normally open main contacts, one normally open auxiliary contact and one normally closed auxiliary contact.

    Normal working conditions and installation conditions

    The ambient air temperature should be -5℃ ~+40℃, with the average temperature of no higher than +35℃ within 24 hours.
    Altitude: not higher than 2000m.
    Atmospheric conditions: when the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature, such as 90% under 20℃. Special measures should be taken for occasional condensation due to temperature change.
    Pollution level: level 3.
    Installation category: category III.
    Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°.
    Impact vibration: the product should be installed and used in a place without obvious shaking, impact and vibration.

    Main parameters and technical performance

    Main parameters and technical performance indicators of the contactor:
    Type ZHCt-0911 ZHCt-1211 ZHCt-1611 ZHCt-1811 ZHCt-2211 ZHCt-2511 ZHCt-3211 ZHCt-3811 ZHCt-4511 ZHCt-5511 ZHCt-7011 ZHCt-8011 ZHCt-10011
    Rated working current 400(380)V AC-3 9 12 16 18 22 25 32 38 45 55 70 85 100
    AC-4 3.5 5 6.5 7.7 8 8.5 12 15 18.5 24 28 37 44
    690(660)V AC-3 6.6 8.9 8.9 12 14 18 21 32 34 39 42 49 49
    AC-4 1.5 2 3 3.8 4 4.4 7.5 8.5 9 12 14 17.3 21.3
    Conventional free air thermal current 20 20 25 32 38 40 50 60 60 80 80 95 95
    Rated insulation voltage 690 690 690 690 690 690 690 690 690 690 690 690 690
    Controllable three-phase squirrel cage motor power (AC-3) kW 230(220)V 2.2 3 3.5 4 5 5.5 7.5 10 11 15 18.5 22 25
    400(380)V 4 5.5 7 7.5 10 11 15 18 18.5 22 30 37 45
    690(660)V 5.5 7.5 9 10 14 15 18.5 22 30 37 37 45 45
    Operating frequency (times/h) Electrical / mechanical endurance AC-3 1200 1200 1200 1200 1200 1200 1200 1200 600 600 600 600 600
    AC-4 300 300 300 300 300 300 300 300 300 300 300 300 300
    Mech. 3600 3600 3600 3600 3600 3600 3600 3600 3600 3600 3600 3600 3600
    Electrical endurance (10,000 times) AC-3 100 100 100 100 80 80 60 60 80 60 60 60 60
    AC-4 20 20 20 20 20 20 20 20 15 15 15 10 10

    Outline and installation dimensions

    bnsmdt2
    Outline and installation dimensions of ZHCt-09~32
    bnsmdt3
    Outline and installation dimensions of ZHCt-45~100
    Contactor type A max B max C max D max E max a b Φ
    ZHCt-0911~1211 47 76 87 120.5 145.5 34/35 56/60 4.5
    ZHCt-1611~1811 47 76 87 125.5 145.5 34/35 50/60 4.5
    ZHCt-2211~2511 57 86 100 138.5 158.5 40 48 4.5
    ZHCt-3211~3811 57 86 100 138.5 158.5 40 48 4.5
    ZHCt-4511~7011 77 129 116 154.5 174.5 40 105 6.5
    ZHCt-4504~7004 84 129 116 154.5 174.5 40 105 6.5
    ZHCt-4508~7008 84 129 127 154.5 174.5 40 105 6.5
    ZHCt-8511~10011 87 129 127 165.5 185.5 40 105 6.5
    ZHCt-8504~10004 96 129 122 160.5 180.5 40 105 6.5
    ZHCt-8508~10008 96 129 135 160.5 180.5 40 105 6.5
    Frequently Asked Questions
    Can these contactors be customized for specific applications?
    Yes, all products of the company can be customized for production according to the user's specific usage scenarios.
    What does the auxiliary contact designation "11" mean for the ZHCt models?
    The "11" designation means the contactor is equipped with three normally open main contacts, one normally open auxiliary contact, and one normally closed auxiliary contact.
    What are the ambient temperature requirements for normal operation?
    The ambient air temperature must remain between -5℃ and +40℃, and the average temperature over a 24-hour period should not exceed +35℃.
    What is the maximum installation altitude and inclination allowed?
    The contactors should be installed at an altitude no higher than 2000 meters, and the inclination between the installation surface and the vertical plane must not exceed ±5°.
    How does humidity affect the working conditions of the contactors?
    At a peak temperature of +40℃, the relative humidity should not exceed 50%. However, higher humidity levels (e.g., up to 90% at +20℃) are acceptable at lower temperatures, provided special measures are taken for occasional condensation.