The CJ12 series and CJ12Z series AC contactors are essential components designed for power circuits operating at a frequency of 50Hz. These contactors support a rated working voltage of up to 380V and a rated working current of up to 600A. They are ideal for remote connection and circuit breaking in electrical equipment, especially for cranes used in metallurgical and steel rolling industries. Additionally, these contactors facilitate frequent starting, stopping, reversing, and reconfiguring of AC motors. As a leading factory and supplier in China, we ensure that our products meet the highest quality standards for various industrial applications

    Type and meaning

    CJ12 series and derived CJ12Z series AC contactors

    Normal working conditions and installation conditions

    The ambient air temperature should be -5'℃ -+40'℃ , with the average temperature of no higher than +35'℃ within 24 hours.
    Altitude: not higher than 2000m.
    Atmospheric conditions: when the highest temperature is +40'℃c, the relative humidity of the air should not be higher than 50%; A higherrelative humidity is allowed at a lower temperature, such as 90% under 20'c Special measures should be taken for occasional condensationdue to temperature change;
    Pollution level: level 3.
    Installation category: category II;
    Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°.
    Impact vibration: the product should be installed and used in a place without obvious shaking, impact and vibration.
    Technical parameters and performance (see Table 1);
    Contactor applies to the following working systems:
    - 8-hour working system;
    - Intermittent periodic working system, with a load factor of40% (4-pole and 5-pole contactors are only applicable to this working system)
    - Short-time working system;Sucking coil specifications:AC: 50Hz: 127V,220V,380V;DC: 110V,220V;
    Action characteristics:pull-in voltage:(85%-110%)Us:
    release voltage:AC(20%~75%)Us,DC(10%~75%)Us.

    Main parameters and technical performance

    Model Rated insulation and
    working voltage
    Conventional free
    air thermal cufTent(A)
    Rated working current(A) Mechanical endurance
    10 times
    Electrical endurance
    (4C-2)10 times
    Number of
    operating COC Derho
    Auxiliary contacts Type of
    matched fuse
    AC-2 AC-4 Control capacity Auxilhary contact
    Conventional free
    air thermal current(A)
    Number
    C12-100 380 100 100 100 300 15 600 AC 380V100VA
    DC 220V90W
    10 open closed RT16-250
    C12-150 380 150 150 150 300 15 600 2 4 RT16-315
    C12-250 380 250 250 250 300 15 600 3 3 RT16-400
    C12-400 380 400 400 400 100 10 300 4 2 RT16-500
    C12-600 380 600 600 600 100 10 300 5 1 RT16-630
    Notes:
    1. Mechanical endurance: no less than 1×10 times for two-pole products and no less than 1×10 times for four-pole and five-pole products;
    2. Electrical endurance: separately agreed by the supplier and the buyer according to the indicators of electrical endurance of three-pole products for the use categories of AC-3 and AC-4 and of two-pole, four-pole and five-pole products for the use category of AC-2;
    3. For CJ12Z series DC controlled AC contactor, the maximum current specification reaches 400A, and the product body has occupied a pair of normally closed auxiliary contacts.

    Structural features of the product

    CJ12 series AC contactor is of open type, with the plane layout of bars. With electromagnetic system in the right, main contact in the center, and auxiliary contact in the left, it is provided with the rotatable stop gear for easy monitoring and repair.
    The magnetic system of the contactor consists of U-shaped moving and static iron cores and coil. Both moving and static iron cores are equipped with buffer devices, which prolongs the service life of the product.
    For CJ12Z, the DC magnetic system is adopted.
    The main contact system of the contactor adopts a single breakpoint rotating structure, and is equipped with clay arc extinguishing chamber with longitudinal slit, which has good arc extinguishing performance.
    The auxiliary contact adopts bridge-type double breakpoints and is provided with the transparent protective cover. The number of normally open and normally closed contacts can be combined according to Table 1.
    The vulnerable parts of the whole contactor are characterized by simple disassembly and easy maintenance.

    Outline and installation dimensions

    CJ12 series and derived CJ12Z series AC contactors4
    Rated working
    current(A)
    Installation dimensions C Maximum outline dimensions Safe area Mounting
    Screw
    B A(total width) (Total height) (Total depth)
    Level II Level II Level II Level II Level I Level III Level IV Level V L M
    100 274 330 386 442   316 372 430 486 194 195 80 50 M10
    150 307 370 433 496   346 409 473 537 219 207 70 70 M10
    250 335 405 475 545   374 445 516 586 255 230 70 80 M10
    400 360 440 520 600   420 500 581 663 296 274 100 80 M12
    600 404 500 596 692   469 566 664 760 349 334 120 150 M16

    Frequently Asked Questions

    What are the ambient temperature limits for the CJ12 series AC contactors?
    The ambient air temperature should be within the range of -5°C to +40°C. Additionally, the average temperature within a 24-hour period must not exceed +35°C.
    What is the maximum installation altitude for these contactors?
    The contactors are designed to be installed and operated at an altitude not higher than 2000 meters above sea level.
    What are the available coil specifications for the CJ12 series?
    The sucking coil specifications include AC (50Hz) options of 127V, 220V, and 380V, as well as DC options of 110V and 220V.
    How is the magnetic system designed in the CJ12 and CJ12Z contactors?
    The CJ12 series features a magnetic system consisting of U-shaped moving and static iron cores and a coil equipped with buffer devices to prolong service life. For the derived CJ12Z series, a DC magnetic system is adopted.
    What are the structural features of the contactor's main and auxiliary contacts?
    The main contact system adopts a single breakpoint rotating structure with a clay arc extinguishing chamber with longitudinal slit. The auxiliary contacts adopt bridge-type double breakpoints and feature a transparent protective cover.