China CJ19 Series Capacitor Changeover Contactors from Reliable Suppliers & Factory for Reactive Power Compensation
Type and meaning
Normal working conditions and installation conditions
- The ambient air temperature should not exceed +40℃, with the average temperature of no higher than +35℃ within 24 hours. The lower limit of the ambient air temperature should be -5℃. When the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; a higher relative humidity is allowed at a lower temperature.
- The altitude of the installation site should not exceed 2000m.
- Pollution level: level 3.
- Installation category: category II.
- Installation condition: the inclination between the installation surface of the contactor and the vertical plane should not exceed 5°.
- Impact and vibration: the product should be installed in a place without obvious shaking, impact and vibration.
Schematic diagram of wiring
For the schematic diagram of wiring of CJ19 series, please refer to Fig. 1.

L1~L3 should be connected to the power supply side; T1~T3 should be connected to the load side.
Main parameters and technical performance
| CJ19 | 25 | 32 | 43 | 63 | 95 | 115 | 150 | 170 | |
| Rated insulation voltage (Ui) V | 500V | 690V | |||||||
| Rated working voltage (Ue) V | 220V/240V, 380V/400V | ||||||||
| Controllable capacitor Capacity (Qn) Kva | 220V | 6 | 9 | 10 | 15 | 28.8 (240V) | 34.5 (240V) | 46 (240V) | 52 (240V) |
| 380V | 12 | 18 | 20 | 30 | 50 (400V) | 60 (400V) | 80 (400V) | 90 (400V) | |
| Conventional free air thermal current Ith | 25 | 32 | 43 | 63 | 63 | 200 | 200 | 275 | |
| Rated working current (AC-6b) Ie A | 17 | 23 | 29 | 43 | 43 | 87 | 115 | 130 | |
| Inrush current suppression capability | 20Ie | ||||||||
| Control power supply voltage Us V | 110, 127, 220, 380 | ||||||||
| Auxiliary contact | AC-15: 360VA | DC-13: 33W | Ith: 10A | ||||||||
| Operating frequency times/h | 120 | ||||||||
| Electrical endurance 10,000 times | 10 | 2 | |||||||
| Mechanical endurance 10,000 times | 100 | 300 | |||||||
| Dimensions and type | Outline dimensions | Installation dimensions | ||||||
| A | B | C | D | A | B | φ | Calliper gauge | |
| CJ19-25 | 76 | 47 | 125 | 120 | 35 | 50/60 | 4.5 | 35 |
| CJ19-32 | 86 | 58 | 135 | 130 | 40 | 50/60 | ||
| CJ19-43 | 86 | 58 | 135 | 130 | 40 | 50/60 | ||
| CJ19-63 | 128 | 79 | 156 | 150 | 40 | 100/110 | 6.5 | 35/75 |
| CJ19-80 | 128 | 87 | 160 | 200 | 40 | 100/110 | ||
| CJ19-95 | 128 | 87 | 160 | 200 | 40 | 100/110 | ||
Shape and installation dimensions(mm)

Fig.2 Diagram of outline and installation dimensions of CJ19-25, 32, 43
Frequently Asked Questions (FAQ)
What is the meaning of the auxiliary contact digits on the CJ19 contactor?
The number of auxiliary contacts is represented by two digits. The tens digit represents the logarithm of normally open (NO) contacts, and the units digit represents the logarithm of normally closed (NC) contacts.
What are the ambient air temperature limits for installing the CJ19 contactor?
The ambient air temperature must not exceed +40℃, and the average temperature over a 24-hour period should not exceed +35℃. The lower limit for the ambient air temperature is -5℃.
What is the maximum installation altitude for the CJ19 series?
The altitude of the installation site for the CJ19 series capacitor changeover contactor should not exceed 2000 meters.
What is the allowable inclination angle for the installation surface?
The inclination between the installation surface of the CJ19 contactor and the vertical plane should not exceed 5°.
What is the inrush current suppression capability of the CJ19 series?
The CJ19 series contactor features an inrush current suppression capability rated at 20Ie.
What control power supply voltages (Us) are supported?
The CJ19 series supports control power supply voltages (Us) of 110V, 127V, 220V, and 380V.