China CJ19t Switching Capacitor Contactor ZNFO Special Series - Premium Suppliers and Factory for Reactive Power Compensation
Advantage
All products of the company can be customized for production according to user usage scenarios.
Type and meaning
Type and meaning
Annotation:
1. The number of auxiliary contacts is represented by two digits, of which the tens digit is the logarithm of normally open contacts, and the units digit is the logarithm of normally closed contacts.
2. For AC-6b 400vAT, the rated working currents corresponding to various specification codes are 25(18A), 32(24A), 43(29A), 50(36A), 63(48A), 95(58A), 125(87A).
Normal working conditions and installation conditions
- The ambient air temperature should not exceed +40°C, with the average temperature of no higher than +35°C within 24 hours. The lower limit of the ambient air temperature should be -5°C. When the highest temperature is +40°C, the relative humidity of the air should not be higher than 50%. A higher relative humidity is allowed at a lower temperature.
- The altitude of the installation site should not exceed 2000m;
- Pollution level: level 3;
- Installation category: category I;
- Installation condition: the inclination between the installation surface of the contactor and the vertical plane should not exceed 5°.
- Impact and vibration: the product should be installed in a place without obvious shaking, impact and vibration.
Installation wiring diagram
For the schematic diagram of wiring of CJ19t series, please refer to Fig.1.

L1~L3 should be connected to the power supply side; T1~T3 should be connected to the load side.
Main parameters and technical performance
| CJ19t | 25 | 32 | 43 | 63 | 95 | 115 | 150 | 170 | |
|---|---|---|---|---|---|---|---|---|---|
| Rated insulation voltage(Ui)V | 500V | 690V | |||||||
| Rated working voltage(Ue)V | 220V/240V, 380V/400V | ||||||||
| Controllable capacitor Capacity(Qn)Kva | 220V | 6 | 9 | 10 | 15 | 28.8(240V) | 34.5(240V) | 46(240V) | 52(240V) |
| 380V | 12 | 18 | 20 | 30 | 50(400V) | 60(400V) | 80(400V) | 90(400V) | |
| Conventional free air thermal current Ith | 25 | 32 | 43 | 63 | 63 | 200 | 200 | 275 | |
| Rated working current(AC-6b)Ie A | 17 | 23 | 29 | 43 | 43 | 87 | 115 | 130 | |
| Inrush current suppression capability | 20Ie | ||||||||
| Control power supply voltage UsV | 110, 127, 220, 380 | ||||||||
| Auxiliary contact | AC-15:360VA DC-13:33W Ith:10A | ||||||||
| Operating frequency times/h | 120 | ||||||||
| Electrical endurance 10,000 times | 10 | 2 | |||||||
| Mechanical endurance 10,000 times | 100 | 300 | |||||||
| Dimensions and type | Outline dimensions | Installation dimensions | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| A | B | C | D | A | B | φ | Card gauge | |||
| CJ19t-25 | 76 | 47 | 125 | 120 | 35 | 50/60 | 4.5 | 35 | ||
| CJ19t-32 | 86 | 58 | 135 | 130 | 40 | 50/60 | ||||
| CJ19t-43 | 86 | 58 | 135 | 130 | 40 | 50/60 | ||||
| CJ19t-63 | 128 | 79 | 156 | 150 | 40 | 100/110 | 6.5 | 35/75 | ||
| CJ19t-80 | 128 | 87 | 160 | 200 | 40 | 100/110 | ||||
| CJ19t-95 | 128 | 87 | 160 | 200 | 40 | 100/110 | ||||
Outline and installation dimensions
The contactor may be installed by screws or card track.

Diagram of outline and installation dimensions of CJ19t-25,32,43
Frequently Asked Questions (FAQ)
Can the CJ19t series contactor products be customized?
Yes, all products of the company can be customized for production according to the user's specific usage scenarios.
What are the ambient temperature requirements for installation?
The ambient air temperature must not exceed +40°C, and the average temperature over 24 hours should not exceed +35°C. The lower limit for the ambient air temperature is -5°C.
What is the maximum installation altitude allowed for this contactor?
The altitude of the installation site for the contactor should not exceed 2000 meters.
How should the wiring sides (L1~L3 and T1~T3) be connected?
L1~L3 must be connected to the power supply side, and T1~T3 must be connected to the load side.
What are the supported installation methods for the contactor?
The contactor can be installed using either screws or card track, provided the inclination between the installation surface and the vertical plane does not exceed 5°.
What are the pollution level and installation category of the CJ19t series?
The contactor is designed with a pollution level of level 3 and falls under installation category I.