China CJ19t ZNFO Special Series Capacitor Contactor Suppliers - Factory Direct Low-Voltage Reactive Power Solutions
Advantage
All products of the company can be customized for production according to user usage scenarios.
Type and meaning
Type and meaning - Annotations
Annotation:
- The number of auxiliary contacts is represented by two digits, of which the tens digit is the logarithm of normally open contacts, and the units digit is the logarithm of normally closed contacts.
- For AC-6b 400vAT, the rated working currents corresponding to various specification codes are 25(18A), 32(24A), 43(29A), 50(36A), 63(48A), 95(58A), 125(87A).
Normal working conditions and installation conditions
- The ambient air temperature should not exceed +40°C, with the average temperature of no higher than +35°C within 24 hours. The lower limit of the ambient air temperature should be -5°C: When the highest temperature is +40°C, the relative humidity of the air should not be higher than 50%: A higher relative humidity is allowed at a lower temperature.
- The altitude of the installation site should not exceed 2000m;
- Pollution level: level 3;
- Installation category: category I;
- Installation condition: the inclination between the installation surface of the contactor and the vertical plane should not exceed 5°.
- Impact and vibration: the product should be installed in a place without obvious shaking, impact and vibration.
Installation wiring diagram
For the schematic diagram of wiring of CJ19t series, please refer to Fig.1.

L1~L3 should be connected to the power supply side; T1~T3 should be connected to the load side.
Main parameters and technical performance
| CJ19t | 25 | 32 | 43 | 63 | 95 | 115 | 150 | 170 | |
| Rated insulation voltage(Ui)V | 500V | 690V | |||||||
| Rated working voltage(Ue)V | 220V/240V、380V/400V | ||||||||
| Controllable capacitor Capacity(Qn)Kva | 220V | 6 | 9 | 10 | 15 | 28.8(240V) | 34.5(240V) | 46(240V) | 52(240V) |
| 380V | 12 | 18 | 20 | 30 | 50(400V) | 60(400V) | 80(400V) | 90(400V) | |
| Conventional free air thermal current Ith | 25 | 32 | 43 | 63 | 63 | 200 | 200 | 275 | |
| Rated working current(AC-6b)le A | 17 | 23 | 29 | 43 | 43 | 87 | 115 | 130 | |
| Inrush current suppression capability | 20le | ||||||||
| Control power supply voltage UsV | 110、127、220、380 | ||||||||
| Auxiliary contact | AC-15:360VA DC-13:33W Ith:10A | ||||||||
| Operating frequency times/h | 120 | ||||||||
| Electrical endurance 10,000 times | 10 | 2 | |||||||
| Mechanical endurance 10,000 times | 100 | 300 | |||||||
| Dimensions and type | Outline dimensions | Installation dimensions | ||||||||
| A | B | C | D | A | B | φ | Card gauge | |||
| CJ19t-25 | 76 | 47 | 125 | 120 | 35 | 50/60 | 4.5 | 35 | ||
| CJ19t-32 | 86 | 58 | 135 | 130 | 40 | 50/60 | ||||
| CJ19t-43 | 86 | 58 | 135 | 130 | 40 | 50/60 | ||||
| CJ19t-63 | 128 | 79 | 156 | 150 | 40 | 100/110 | 6.5 | 35/75 | ||
| CJ19t-80 | 128 | 87 | 160 | 200 | 40 | 100/110 | ||||
| CJ19t-95 | 128 | 87 | 160 | 200 | 40 | 100/110 | ||||
Outline and installation dimensions
The contactor may be installed by screws or card track.

Diagram of outline and installation dimensions of CJ19t-25,32,43
Frequently Asked Questions (FAQ)
Can these products be customized?
Yes, all products of the company can be customized for production according to specific user usage scenarios.
What are the ambient air temperature limits for normal working conditions?
The ambient air temperature should not exceed +40°C, and the average temperature must not exceed +35°C within 24 hours. The lower limit for the ambient air temperature is -5°C.
What is the maximum installation altitude for these contactors?
The installation site altitude should not exceed 2000 meters above sea level.
How should the wiring be connected based on the diagram?
L1, L2, and L3 must be connected to the power supply side, while T1, T2, and T3 must be connected to the load side.
What are the installation methods for the contactor?
The contactor can be securely installed using either screws or a card track system.
What is the allowed inclination angle during installation?
The inclination between the installation surface of the contactor and the vertical plane should not exceed 5°.