China CJ19t ZNFO Special Series Switching Capacitor Contactor - Reliable Suppliers and Factory for Reactive Power Solutions

The CJ19t series capacitor changeover contactor is an essential component for electric power circuits operating at 50Hz or 60Hz and a rated voltage of up to 400V. This versatile contactor is specifically designed for efficiently controlling low-voltage reactive power compensation equipment, allowing for the seamless operation and disconnection of low-voltage shunt capacitors, Manufactured by leading China suppliers, the contactor features an advanced inrush current suppression device, which significantly mitigates the effects of closing inrush currents on capacitors and helps to reduce over-voltage during operation. As a reliable factory, we ensure high-quality production standards to meet the demands of various applications in electric power systems. Trust our CJ19t series contactor for safe and effective control of your capacitor systems

    Advantage

    All products of the company can be customized for production according to user usage scenarios.

    Type and meaning

    hkugtre

    Type and meaning

    Annotation:
    • 1. The number of auxiliary contacts is represented by two digits, of which the tens digit is the logarithm of normally open contacts, and the units digit is the logarithm of normally closed contacts.
    • 2. For AC-6b 400vAT, the rated working currents corresponding to various specification codes are 25(18A), 32(24A), 43(29A), 50(36A), 63(48A), 95(58A), 125(87A).

    Normal working conditions and installation conditions

    • The ambient air temperature should not exceed +40°C, with the average temperature of no higher than +35°C within 24 hours. The lower limit of the ambient air temperature should be -5°C: When the highest temperature is +40°C, the relative humidity of the air should not be higher than 50%: A higher relative humidity is allowed at a lower temperature.
    • The altitude of the installation site should not exceed 2000m;
    • Pollution level: level 3;
    • Installation category: category I;
    • Installation condition: the inclination between the installation surface of the contactor and the vertical plane should not exceed 5°.
    • Impact and vibration: the product should be installed in a place without obvious shaking, impact and vibration.

    Installation wiring diagram

    For the schematic diagram of wiring of CJ19t series, please refer to Fig.1.
    fgerv2
    L1~L3 should be connected to the power supply side; T1~T3 should be connected to the load side.

    Main parameters and technical performance

    CJ19t 25 32 43 63 95 115 150 170
    Rated insulation voltage(Ui)V 500V 690V
    Rated working voltage(Ue)V 220V/240V, 380V/400V
    Controllable capacitor Capacity(Qn)Kva 220V 6 9 10 15 28.8(240V) 34.5(240V) 46(240V) 52(240V)
    380V 12 18 20 30 50(400V) 60(400V) 80(400V) 90(400V)
    Conventional free air thermal current Ith 25 32 43 63 63 200 200 275
    Rated working current(AC-6b)le A 17 23 29 43 43 87 115 130
    Inrush current suppression capability 20le
    Control power supply voltage UsV 110, 127, 220, 380
    Auxiliary contact AC-15:360VA DC-13:33W Ith:10A
    Operating frequency times/h 120
    Electrical endurance 10,000 times 10 2
    Mechanical endurance 10,000 times 100 300
    Dimensions and type Outline dimensions Installation dimensions
      A B C D A B φ Card gauge
    CJ19t-25 76 47 125 120 35 50/60 4.5 35
    CJ19t-32 86 58 135 130 40 50/60
    CJ19t-43 86 58 135 130 40 50/60
    CJ19t-63 128 79 156 150 40 100/110 6.5 35/75
    CJ19t-80 128 87 160 200 40 100/110
    CJ19t-95 128 87 160 200 40 100/110

    Outline and installation dimensions

    The contactor may be installed by screws or card track.
    fgerv3
    Diagram of outline and installation dimensions of CJ19t-25,32,43
    Frequently Asked Questions (FAQ)
    Can these products be customized for specific applications?
    Yes, all products of the company can be customized for production according to specific user usage scenarios.
    What are the ambient temperature requirements for installation?
    The ambient air temperature must not exceed +40°C, and the average temperature over 24 hours should not exceed +35°C. The lower temperature limit is -5°C. At +40°C, relative humidity should not exceed 50%, though higher humidity is permitted at lower temperatures.
    What is the maximum installation altitude for the CJ19t series?
    The altitude of the installation site for the CJ19t series contactor should not exceed 2000 meters.
    How should the wiring be connected on the CJ19t series contactors?
    Based on the schematic diagram of wiring, L1~L3 terminals must be connected to the power supply side, and T1~T3 terminals must be connected to the load side.
    What mounting options are available for installation?
    The contactor is designed for versatile installation and can be mounted using either screws or standard card tracks (35mm or 35/75mm card gauge depending on the model).