China CJX1 AC Contactor Suppliers & Factory - 50/60Hz, 660V, 400A Reliable Circuit Control Solutions
Type and meaning
Normal working conditions and installation conditions
- Altitude: not higher than 2000m;
- The ambient air temperature should be -5℃ ~+40℃, with the average temperature of no higher than +35℃ within 24 hours.
- When the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature, such as not higher than 90% under +20℃. Special measures should be taken for occasional condensation due to temperature change;
- Pollution level: level 3;
- Installation category: category II;
- Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°;
- The product should be installed in a place without obvious shaking, impact and vibration.
Main parameters and technical performance
| Type | CJX1 -9 | CJX1 -12 | CJX1 -16 | CJX1 -22 | CJX1 -32 | CJX1 -45 | CJX1 -63 | CJX1 -75 | CJX1 -85 | CJX1 -110 | CJX1 -140 | CJX1 -170 | CJX1 -205 | CJX1 -250 | CJX1 -300 | CJX1 -400 | ||
| Rated insulation voltage U iv | 660 | |||||||||||||||||
| Rated working current le(A) | AC-3 | 380 | 9 | 12 | 16 | 22 | 32 | 45 | 63 | 75 | 85 | 110 | 140 | 170 | 205 | 250 | 300 | 400 |
| 660 | 7.2 | 9.5 | 13.5 | 13.5 | 18 | 45 | 63 | 75 | 75 | 110 | 110 | 170 | 170 | 200 | 250 | 320 | ||
| AC-4 | 380 | 3.3 | 4.3 | 7.7 | 8.5 | 12 | 24 | 28 | 4 | 42 | 54 | 68 | 75 | 96 | 110 | 125 | 150 | |
| 660 | 1.4 | 1.9 | 3.5 | 4 | 7.5 | 12 | 14 | 17 | 21 | 27 | 35 | 42 | 67 | 95 | 110 | 115 | ||
| Controllable power Pe(kW) | AC-3 | 380 | 4 | 5.5 | 7.5 | 11 | 15 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | 110 | 132 | 160 | 200 |
| 660 | 5.5 | 7.5 | 11 | 11 | 15 | 37 | 55 | 55 | 55 | 90 | 90 | 160 | 160 | 185 | 220 | 315 | ||
| AC-4 | 380 | 1.5 | 22 | 4 | 4 | 5.5 | 11 | 11 | 18.5 | 22 | 30 | 37 | 37 | 45 | 55 | 55 | 75 | |
| 660 | 11 | 15 | 3 | 4 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 55 | 75 | 90 | 110 | |||
| Conventional thermal current > Ith | A | 20 | 30 | 45 | 70 | 90 | 150 | 170 | 205 | 250 | 300 | 400 | ||||||
| Rated operating frequency times h | AC-3 | 1200 | 600 | 300 | ||||||||||||||
| AC-4 | 300 | 150 | ||||||||||||||||
| Mechanical endurance (10,000 times) | 1000 | 800 | 600 | |||||||||||||||
| Electrical endurance (10,000 times) | AC-3 | 100 | 80 | 60 | ||||||||||||||
| 20 | 15 | 10 | ||||||||||||||||
| Specification of matched fuse(RT16)A | 16 | 20 | 25 | 32 | 50 / 80 | 100 / 125 | 160 | 200 | 200 | 250 | 250 | 300 | 400 | 500 | ||||
The rated control power supply voltage Us of the contactor at AC 50/60 Hz is: 36/42, 48/58, 110/132, 127/152, 220/264, 380/456(V).
The contactor coil can reliably hold at 85%~110% of the rated control power supply voltage, and can reliably release at 20%~75% of the rated control power supply voltage.
For the auxiliary circuit, the rated insulation voltage (Ui) is 660V; the conventional thermal current (Ith) is 10A; Other parameters are shown in Table 3.
| Use category | Rated working voltage Ue (V) | Rated working current Ie (A) | Rated control power | |
| AC (VA) | DC (W) | |||
| AC-15 | 36 | 10 | 360 | - |
| 110 | 3.2 | |||
| 220 | 1.64 | |||
| 380 | 0.95 | |||
| DC-13 | 48 | 0.69 | - | 33 |
| 110 | 0.3 | |||
| 220 | 0.15 | |||
Outline and installation dimensions

Fig.1 Outline and installation dimensions of CJX1-9/32
| Type | a max | b | c max | d | e max | g | Φ |
| CJX1-9/12 | 79 | 60±0.60 | 46 | 35±0.50 | 106 | 8 | 4.8 (+0.48) |
| CJX1-16/22 | 89 | 75±0.60 | 46 | 35±0.50 | 116 | 8 | |
| CJX1-32 | 90 | 75±0.60 | 74 | 50±0.55 | 109 | 8 | 4.8 (+0.48) |
Frequently Asked Questions (FAQ)
QWhat is the maximum altitude limit for installing the CJX1 series AC contactor?
The installation altitude for the CJX1 series AC contactor should not exceed 2000 meters above sea level.
QWhat are the ambient temperature and humidity requirements for proper operation?
The ambient air temperature must be between -5℃ and +40℃ (with a 24-hour average of ≤ +35℃). Relative humidity should not exceed 50% at +40℃, though higher humidity (up to 90%) is allowed at lower temperatures like +20℃.
QWhat are the coil operating voltage ranges for holding and releasing?
The contactor coil reliably holds at 85% to 110% of the rated control power supply voltage (Us) and reliably releases within 20% to 75% of Us.
QWhat is the rated insulation voltage (Ui) for the auxiliary circuit?
The auxiliary circuit features a rated insulation voltage (Ui) of 660V and a conventional thermal current (Ith) of 10A.
QWhat are the installation orientation and environmental restrictions?
The contactor should be installed with an inclination of no more than ±5° relative to the vertical plane, in a location free from significant shaking, impact, or vibration.