China CJX2 AC Contactor - 50Hz/60Hz, 690V, 95A | Leading Suppliers & Factory for Electromagnetic Starters
Type and meaning
Note 1:
09A-95A adopts the number of auxiliary contacts, while 115A-800A adopts the number of poles.
10 means three normally open main contacts and one normally open auxiliary contact (32A and below);
01 means three normally open main contacts and one normally closed auxiliary contact (32A and below);
11 means three normally open main contacts, one normally open auxiliary contact and one normally closed auxiliary contact (40A and above).
Normal working conditions and installation conditions
- The ambient air temperature should be -5℃~+40℃, with the average temperature of no higher than +35℃ within 24 hours.
- Altitude: not higher than 2000m;
- Atmospheric conditions: when the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature such as 90% under 20℃. Special measures should be taken for occasional condensation due to temperature change.
- Pollution level: level 3;
- Installation category: category III;
- Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°;
- Impact vibration: the product should be installed and used in a place without obvious shaking, impact and vibration.
Main parameters and technical performance
Main parameters and technical performance index contactor
| Type | CJX2-09 | CJX2-12 | CJX2-18 | CJX2-25 | CJX2-32 | CJX2-40 | CJX2-50 | CJX2-65 | CJX2-80 | CJX2-95 | ||
| Rated working current | 400(380)V | AC-3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
| AC-4 | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | ||
| 690(660)V | AC-3 | 6.6 | 8.9 | 12 | 18 | 21 | 34 | 39 | 42 | 49 | 49 | |
| AC-4 | 1.5 | 2 | 3.8 | 4.4 | 7.5 | 9 | 12 | 14 | 17.3 | 21.3 | ||
| Conventional free air thermal current | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 95 | 95 | ||
| Rated insulation voltage | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | ||
| Controllable three-phase squirrel cage motor power(AC-3)kW | 230(220)V | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 | |
| 400(380)V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | ||
| 690(660)V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 37 | 37 | 45 | 45 | ||
| Operating frequency (times/h) | Electrical endurance, mechanical endurance | AC-3 | 1200 | 1200 | 1200 | 1200 | 600 | 600 | 600 | 600 | 600 | 600 |
| AC-4 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | ||
| - | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | ||
| Electrical endurance (10,000 times) | AC-3 | 100 | 100 | 100 | 100 | 80 | 80 | 60 | 60 | 60 | 60 | |
| AC-4 | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 15 | 10 | 10 | ||
Outline and installation dimensions

Outline and installation dimensions of CJX2-09~32

Outline and installation dimensions of CJX2-40~95
| Contactor type | A max | B max | C max | D max | E max | a | b | φ |
|---|---|---|---|---|---|---|---|---|
| CJX2-09~12 | 47 | 76 | 82 | 120.5 | 140.5 | 34/35 | 56/60 | 4.5 |
| CJX2-18 | 47 | 76 | 87 | 125.5 | 145.5 | 34/35 | 50/60 | 4.5 |
| CJX2-25 | 57 | 86 | 95 | 133.5 | 153.5 | 40 | 48 | 4.5 |
| CJX2-32 | 57 | 86 | 100 | 138.5 | 158.5 | 40 | 48 | 4.5 |
| CJX2-4011~6511 | 77 | 129 | 116 | 154.5 | 174.5 | 40 | 105 | 6.5 |
| CJX2-4004~6504 | 84 | 129 | 116 | 154.5 | 174.5 | 40 | 105 | 6.5 |
| CJX2-40086~508 | 84 | 129 | 127 | 154.5 | 174.5 | 40 | 105 | 6.5 |
| CJX2-8011~9511 | 87 | 129 | 127 | 165.5 | 185.5 | 40 | 105 | 6.5 |
| CJX2-8004~9504 | 96 | 129 | 122 | 160.5 | 180.5 | 40 | 105 | 6.5 |
| CJX2-8008~9508 | 96 | 129 | 135 | 160.5 | 180.5 | 40 | 105 | 6.5 |
Frequently Asked Questions (FAQ)
What do the code designations "10", "01", and "11" mean for CJX2 contactors?
For contactors rated at 32A and below, "10" designates 3 normally open main contacts and 1 normally open auxiliary contact, while "01" designates 3 normally open main contacts and 1 normally closed auxiliary contact. For contactors rated at 40A and above, "11" designates 3 normally open main contacts, 1 normally open auxiliary contact, and 1 normally closed auxiliary contact.
What are the ambient air temperature limits for installing the CJX2 series AC contactor?
The ambient air temperature must be kept within the range of -5℃ to +40℃. Additionally, the average temperature over a 24-hour period should not exceed +35℃.
Is there an altitude limitation for the installation of these contactors?
Yes, the installation altitude for the CJX2 series AC contactors should not be higher than 2000 meters above sea level.
How does humidity affect the operation and installation of the contactor?
At the maximum temperature of +40℃, the relative humidity should not exceed 50%. However, higher relative humidity is permitted at lower temperatures (e.g., up to 90% at 20℃). Special measures must be implemented to manage occasional condensation caused by temperature fluctuations.
What is the allowed inclination angle for the installation surface?
The inclination between the vertical plane and the mounting surface of the CJX2 series AC contactor must not exceed ±5°.
What are the pollution level and installation category ratings for this product?
The CJX2 series AC contactor is rated for Pollution Level 3 and falls under Installation Category (Overvoltage Category) III.