China CJX2-N Interlocking Contactor - Reliable Suppliers and Factory for AC Motors Control up to 954A
Type and meaning
Normal working conditions and installation conditions
The altitude of the installation site should not exceed 2000m;
The ambient air temperature should not be higher than+40℃ and not be lower than-5℃.
When the highest temperature is +40℃, the relative humidity of the air on the installation site should not be higher than 50%;A higher relative humidity is lowed at a lower temperature:In the wettest month.the monthly average minimum temperature should not exceed +20℃ and the average maximum relative humidity should not exceed 90%. Measures should betaken for condensation on the product due to temperature change.
The inclination between the installation surface and the vertical plane should not exceed ±22. 5~.
Pollution level:level 3;
The product should be installed in a place without obvious shaking, impact and vibration.
Structural features of the product
The action mechanism is of direct acting type, and the contact is of double breakpoints.
With the combination function, all surfaces except for the installation surface may be additionally provided with accessories.
Auxiliary contact sets maybe additionally installed on both sides.
Auxiliary contact sets or air damping, type time relays may be additionally installed on the upper side.
The coil terminal may be additionally provided with various functional modules such as time delay units.
Both mechanical and electrical interlocking can be achieved.
Main parameters and technical performance
| Type | CJX2- 09N | CJX2- 12N | CJX2- 18N | NCJX 2- 25N | CJX2- 32N | CJX2- 40N | CJX2- 50N | CJX2- 65N | CJX2- 80N | CJX2- 95N | ||||||
| Rated working current A | 380V | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 | |||||
| 660V | 20 | 8.9 | 12 | 18 | 21 | 34 | 39 | 42 | 49 | 55 | ||||||
| Conventional thermal current It hA | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 125 | 125 | ||||||
| Rated working voltage U eV | 380 | |||||||||||||||
| Rated insulation voltage U iV | 690 | |||||||||||||||
| AC-3 | Electrical endurance 10*times | 100 | 100 | 100 | 100 | 80 | 80 | 80 | 80 | 60 | 60 | |||||
| Operating frequency times/h | 1200 | 1200 | 1200 | 1200 | 600 | 600 | 600 | 600 | 600 | 600 | ||||||
| AC-4 | Electrical endurance 10*times | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 15 | 10 | 10 | |||||
| Operating frequency times/h | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | ||||||
| Rated working current leA | 380V | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | |||||
| 660V | 1.5 | 2 | 2.8 | 4.4 | 7.5 | 9 | 12 | 14 | 17.3 | 21.3 | ||||||
| Auxiliary contact | Electrical endurance | AC-151360VA | The same as the electrical endurance of the main contact(AC-3) | |||||||||||||
| DC-13(33W) | ||||||||||||||||
| Minimum load for connection | 6V10mA | |||||||||||||||
| Coil | Rated control voltage UsV | 24、48、110、220、380 | ||||||||||||||
| Pull-in voltage | (0.85~1.10)Us | |||||||||||||||
| Release voltage | (0.20~0.75)Us | |||||||||||||||
| Coil power | Pull-in | 70 | 70 | 70 | 110 | 110 | 200 | 200 | 200 | 200 | 200 | |||||
| Holding | 8 | 8 | 8 | 11 | 11 | 20 | 20 | 20 | 20 | 20 | ||||||
Outline and installation dimensions

Note: C1: CJX2-N+F4 | C2: CJX2+SK2-2/3
| Interlocking contactor type | A max | B max | C max | D max | C1 | C2 | a | b |
| CJX2-09N, 12N | 112 | 76 | 87 | 86 | 115 | 134 | 96 | 50 |
| CJX2-18N | 112 | 76 | 92 | 86 | 120 | 139 | 96 | |
| CJX2-25N | 134 | 86 | 102 | 98 | 130 | 149 | 112 | 60 |
| CJX2-32N | 134 | 86 | 120 | 100 | 135 | 154 | 112 |

Note: C1: CJX2-N+F4 | C2: CJX2+SK2-2/3
| Interlocking contactor type | A max | B max | C max | D max | C1 | C2 | a | ai | b |
| CJX2-10N, 50N, 65N | 176 | 128 | 145 | 138 | 149 | 168 | 49 | 90±0.70 | 100 / 110 |
| CJX2-80N, 95N | 190 | 128 | 162 | 146 | 160 | 179 | 56 | 90±0.70 | 100 / 110 |
Tightening torque for verifying mechanical strength of connection terminal of AC contactor
| Basic specification | Thread diameter mm | Tightening torque N |
| 9~12 | 3.5 | 0.8 |
| 16-25 | 4 | 1.2 |
| 21-50 | 6 | 2.5 |
| 63~125 | 6 | 3.0 |
| 160~250 315~500 | 8 / 10 | 6.0 / 10.0 |
| 630~1000 | 12 | 14.0 |
Frequently Asked Questions (FAQ)
What is the maximum installation altitude for the CJX2-N series contactor?
The altitude of the installation site should not exceed 2000 meters.
What are the ambient temperature limits for normal working conditions?
The ambient air temperature should not be higher than +40℃ and must not be lower than -5℃.
Can this contactor achieve both mechanical and electrical interlocking?
Yes, both mechanical and electrical interlocking can be successfully achieved with the CJX2-N series.
What is the rated insulation voltage (Ui) for these contactors?
The rated insulation voltage (Ui) is 690V.
What is the required tightening torque for a basic specification of 9~12?
For a basic specification of 9~12, the thread diameter is 3.5mm and the tightening torque is 0.8 N.