China Suppliers Factory AC Contactor CJ40 ZNFO Traditional Series for 50/60Hz Circuits up to 1000A
Type and meaning
Type and meaning
The auxiliary code is composed of 5 parts, which are selected in the following order as needed:
- In the first part, “y” means general type, “N” (can be omitted) means reversible type;
- In the second part, 1 digit is used to indicate the number of poles of the main circuit: 3 and 4 respectively indicate 3 and 4 poles, and 3 can be omitted;
- In the third part, 2 digits are used to indicate the highest rated working voltage, "06" (which can be omitted) indicates 690V, "11" indicates 1140V;
- In the fourth part indicates the rated control power supply voltage, with letters "Ac" indicating alternating current 50 Hz and "Dc" indicating direct current. The value of the rated control power supply voltage is behind the letters, but “AC380” can be omitted;
- In the fifth part, the letter "□" and two digits are used together to indicate the type and number of auxiliary contacts, of which the first digit indicates the number of pairs of normally open auxiliary contacts and the second digit indicates the number of pairs of normally closed auxiliary contacts, but “□42” can be omitted.
Normal working conditions and installation conditions
- The altitude of the installation site should not exceed 2000m;
- The ambient air temperature should not be higher than +40℃ and not be lower than -5℃;
- When the highest temperature is +40℃, the relative humidity of the air on the installation site should not be higher than 50%; A higher relative humidity is allowed at a lower temperature; In the wettest month, the monthly average minimum temperature should not exceed +20℃, and the average maximum relative humidity should not exceed 90%. Measures should be taken for condensation on the product due to temperature change;
- The inclination between the installation surface and the vertical plane should not exceed ±5°.
- Pollution level: level 3;
- The product should be installed in a place without obvious shaking, impact and vibration.
Structural features of the product
CJ40-63~1000 AC contactor adopts the structure of oven type, normal installation, direct acting and double breakpoints. The auxiliary contacts are installed on both sides of the main contact as independent components, which are electrically separated; The iron core is a U-shaped structure with the permanent air gap. The base is made of aluminum alloy die-casting (for CJ40-630A and above), which is installed by screws: But the base of CJ40-63~125 is made of unsaturated polyester glass fiber reinforced molding compound, which may be installed by screws or by “TH75” guide rail. With the advantages of high breaking capacity and high reliability, etc., the arc extinguishing chamber is made of arc-resistant plastic and iron grid.
Outline and installation dimensions
Outline and installation dimensions of CJ40-63~1000 AC contactor
| Product type | Outline dimensions (Max) | Installation dimensions | Installation rail | Installation area F min | |||||
|---|---|---|---|---|---|---|---|---|---|
| A | B | C | a | b | φ | 380V | 660v | ||
| CJ40-63-125 | 116 | 143 | 154 | 100 | 90 | 5.8 | Th75 | 20 | 40 |
| CJ40-160-200 | 146 | 186 | 184 | 130 | 130 | 9 | - | 30 | 40 |
| CJ40-250 | 40 | 60 | |||||||
| CJ40-315-400 | 190 | 235 | 230 | 160 | 150 | 9 | 40 | 60 | |
| CJ40-500 | 50 | 70 | |||||||
| CJ40-630-1250 | 245 | 345 | 288 | 210 | 180 | 11 | 0 | 0 | |
| CJ40-63/4~125/4 | 143 | 143 | 154 | 128 | 90 | 5.8 | Th75 | 20 | 40 |
| CJ40-63/4~200/4 | 187 | 186 | 184 | 170 | 130 | 9 | - | 30 | 40 |
| CJ40-250-4 | 40 | 60 | |||||||
| CJ40-315/4~400/4 | 236 | 235 | 230 | 216 | 150 | 9 | 40 | 60 | |
| CJ40-500/4 | 50 | 70 | |||||||
Main parameters and technical performance
| Type and specification | Frame code | Ui V |
Ith A |
Ie (A) under intermittent periodic duty | AC-4 (A) |
Pe (kW) under AC-3 | Ie (A) under different intermittent duty | |||
|---|---|---|---|---|---|---|---|---|---|---|
| AC-1 | AC-2 | AC-3 | ||||||||
| CJ40-63 | 125 | 220 | 80 | 80 | 63 | 63 | 63 | 18.5 | 80 | |
| 380 | 30 | |||||||||
| CJ40-80 | 660 | |||||||||
| 220 | 80 | 80 | 80 | |||||||
| 380 | ||||||||||
| CJ40-100 | 660 | 63 | 63 | 63 | 55 | |||||
| 220 | 125 | 125 | 100 | 100 | 100 | 30 | 125 | |||
| 380 | ||||||||||
| CJ40-125 | 660 | 80 | 80 | 80 | ||||||
| 220 | 125 | 125 | 125 | |||||||
| 380 | 10 | |||||||||
| 660 | 80 | 80 | 80 | |||||||
| CJ40-160 | 250 | 690 | 220 | 250 | 250 | 160 | 160 | 160 | 45 | 250 |
| CJ40-200 | 380 | 75 | ||||||||
| 660 | 125 | 125 | 125 | 110 | ||||||
| 220 | 200 | 200 | 200 | 55 | ||||||
| CJ40-250 | 380 | 90 | ||||||||
| 660 | 125 | 125 | 125 | 110 | ||||||
| 220 | 250 | 250 | 250 | 75 | ||||||
| 380 | 225 | 132 | ||||||||
| 660 | 125 | 125 | 125 | 110 | ||||||
| CJ40-315 | 500 | 690 | 220 | 500 | 500 | 315 | 315 | 315 | 90 | 500 |
| CJ40-400 | 380 | 250 | 160 | |||||||
| 660 | 300 | |||||||||
| CJ40-500 | 220 | 400 | 400 | 400 | 110 | |||||
| 380 | 315 | 220 | ||||||||
| 660 | 315 | 315 | 300 | |||||||
| 220 | 500 | 500 | 500 | 150 | ||||||
| 380 | 400 | 280 | ||||||||
| 660 | 315 | 315 | 315 | 300 | ||||||
| CJ40-630 | 1000 | 690 | 220 | 800 | 630 | 630 | 630 | 630 | 200 | 630 |
| CJ40-800 | 380 | 500 | 335 | |||||||
| CJ40-1000 | 660 | 500 | 500 | 500 | 475 | |||||
| 220 | 800 | 800 | 800 | 800 | 250 | 800 | ||||
| 380 | 630 | 450 | ||||||||
| CJ40-1250 | 1250 | 660 | 500 | 500 | 500 | 475 | ||||
| 220 | 1000 | 1000 | 1000 | 1000 | 1000 | 360 | 1000 | |||
| 380 | 550 | |||||||||
| 660 | 630 | 630 | 500 | 570 | ||||||
| 220 | 1250 | 1250 | 1250 | 1250 | 1250 | 375 | 1250 | |||
| 380 | 600 | |||||||||
| 660 | 800 | 800 | 600 | 630 | ||||||
| CJ40-125/11 | 1250 | 1140 | 1140 | 125 | 125 | 40 | 40 | 40 | 55 | 125 |
| CJ40-250/11 | 250 | 1140 | 250 | 250 | 80 | 80 | 80 | 110 | 250 | |
| CJ40-500/11 | 500 | 1140 | 500 | 500 | 160 | 160 | 160 | 220 | 500 | |
| CJ40-1000/11 | 1000 | 1140 | 1000 | 1000 | 400 | 600 | 1000 | |||
Frequently Asked Questions (FAQ)
The model designation represents the physical structure and electrical setup, including the contactor type (reversible or general), number of main poles, maximum rated working voltage, control power supply voltage, and the configuration of the auxiliary contacts.
The installation site altitude for standard operation should not exceed 2000 meters above sea level.
The ambient air temperature must remain within the range of -5℃ to +40℃ for standard operation and longevity.
At +40℃, relative humidity should not exceed 50%. Higher relative humidity is permitted at lower temperatures (up to 90% average in the wettest month at +20℃), provided measures are taken to prevent condensation.
They feature an oven-type, direct-acting design with double breakpoints. The auxiliary contacts are independent components electrically separated on both sides of the main contact, and the U-shaped iron core provides a permanent air gap.
Yes, the base of the CJ40-63~125 models is made of unsaturated polyester glass fiber reinforced molding compound, allowing installation via screws or on a "TH75" guide rail.