0102030405
China ZHC40 ZNFO Transcender Series AC Contactor - 690V/1140V, 1000A Suppliers and Factory
Advantage
All products of the company can be customized for production according to user usage scenarios.
Type and meaning
The auxiliary code is composed of 5 parts, which are selected in the following order as needed:
- First part: "Y" means general type; "N" (can be omitted) means reversible type.
- Second part: 1 digit is used to indicate the number of poles of the main circuit: 3 and 4 respectively indicate 3 and 4 poles, and 3 can be omitted.
- Third part: 2 digits are used to indicate the highest rated working voltage: "06" (which can be omitted) indicates 690V; "11" indicates 1140V.
- Fourth part: Indicates the rated control power supply voltage, with letters "AC" indicating alternating current 50Hz and "DC" indicating direct current. The value of the rated control power supply voltage is behind the letters, but "AC380" can be omitted.
- Fifth part: The letter "F" and two digits are used together to indicate the type and number of auxiliary contacts, of which the first digit indicates the number of pairs of normally open auxiliary contacts and the second digit indicates the number of pairs of normally closed auxiliary contacts, but "F 42" can be omitted.
Note: This item includes two parts, i.e. the number of main contacts and the number of auxiliary contacts, which are indicated by number respectively, as shown in the diagram below:
(-□□-□□) indicates: - number of normally open main contacts, number of normally closed main contacts - number of normally open auxiliary contacts, number of normally closed auxiliary contacts.
Normal working conditions and installation conditions
- The altitude of the installation site should not exceed 2000m.
- The ambient air temperature should not be higher than +40℃ and not be lower than -5℃.
- When the highest temperature is +40℃, the relative humidity of the air on the installation site should not be higher than 50%. A higher relative humidity is allowed at a lower temperature. In the wettest month, the monthly average minimum temperature should not exceed +20℃, and the average maximum relative humidity should not exceed 90%. Measures should be taken for condensation on the product due to temperature change.
- The inclination between the installation surface and the vertical plane should not exceed ±5°.
- Pollution level: level 3.
- The product should be installed in a place without obvious shaking, impact and vibration.
Structural features of the product
ZHC40-63~1000 AC contactor adopts the structure of open type, normal installation, direct acting and double breakpoints. The auxiliary contacts are installed on both sides of the main contact as independent components, which are electrically separated; The iron core is a U-shaped structure with the permanent air gap. The base is made of aluminum alloy die-casting (for ZHC40-6304 and above), which is installed by screws; But, the base of ZHC40-63~125 is made of unsaturated polyester glass fiber reinforced molding compound, which may be installed by screws or by “TH75” guide rail. With the advantages of high breaking capacity and high reliability, etc., the arc extinguishing chamber is made of arc resistant plastic and iron grid.
Outline and installation dimensions

ZHC40-63~1000 AC contactor appearance and installation dimensions
| Product type | Outline dimensions (Max) | Installation dimensions | Installation rail | Installation area F min | |||||
|---|---|---|---|---|---|---|---|---|---|
| A | B | C | a | b | φ | 380V | 660V | ||
| ZHC40-63-125 | 116 | 143 | 154 | 100 | 90 | 5.8 | Th75 | 20 | 40 |
| ZHC40-160-200 | 146 | 186 | 184 | 130 | 130 | 9 | - | 30 | 40 |
| ZHC40-250 | 40 | 60 | |||||||
| ZHC40-315-400 | 190 | 235 | 230 | 160 | 150 | 9 | - | 40 | 60 |
| ZHC40-500 | 50 | 70 | |||||||
| ZHC40-630-1250 | 245 | 345 | 288 | 210 | 180 | 11 | - | 0 | 0 |
| ZHC40-63/4~125/4 | 143 | 143 | 154 | 128 | 90 | 5.8 | Th75 | 20 | 40 |
| ZHC40-63/4~200/4 | 187 | 186 | 184 | 170 | 130 | 9 | - | 30 | 40 |
| ZHC40-250-4 | 40 | 60 | |||||||
| ZHC40-315/4~400/4 | 236 | 235 | 230 | 216 | 150 | 9 | - | 40 | 60 |
| ZHC40-500/4 | 50 | 70 | |||||||
Main parameters and technical performance
| Type and specifications | Frame code | U (V) | Voltage (V) | Ith (A) | Ie (A) under intermittent periodic working | Pe (kW) under AC-3 | Ie (A) under different intermittent working systems | |||
|---|---|---|---|---|---|---|---|---|---|---|
| AC-1 | AC-2 | AC-3 | AC-4 | |||||||
| ZHC-63 | 125 | 690 | 220 | 80 | 80 | 63 | 63 | 63 | 18.5 | 80 |
| ZHC-80 | 380 | 30 | ||||||||
| ZHC-100 | 660 | - | ||||||||
| ZHC-63 | 220 | 80 | 80 | 80 | - | |||||
| ZHC-80 | 380 | - | ||||||||
| ZHC-100 | 660 | 63 | 63 | 63 | 55 | |||||
| ZHC-125 | 220 | 125 | 125 | 100 | 100 | 100 | 30 | 125 | ||
| ZHC-125 | 380 | - | ||||||||
| ZHC-125 | 660 | 80 | 80 | 80 | - | |||||
| ZHC-125 | 220 | 125 | 125 | 25 | - | |||||
| ZHC-125 | 380 | 10 | - | |||||||
| ZHC-125 | 660 | 80 | 80 | 80 | - | |||||
| ZHC-160 | 250 | 690 | 220 | 250 | 250 | 160 | 160 | 160 | 45 | 250 |
| ZHC-200 | 380 | 75 | ||||||||
| ZHC-250 | 660 | 125 | 125 | 125 | 110 | |||||
| ZHC-200 | 220 | 200 | 200 | 200 | 55 | |||||
| ZHC-250 | 380 | 90 | ||||||||
| ZHC-250 | 660 | 125 | 125 | 125 | 10 | |||||
| ZHC-250 | 220 | 250 | 250 | 250 | 75 | |||||
| ZHC-250 | 380 | 225 | 132 | |||||||
| ZHC-250 | 660 | 125 | 125 | 125 | 110 | |||||
| ZHC-315 | 500 | 690 | 220 | 500 | 500 | 315 | 315 | 315 | 90 | 500 |
| ZHC-400 | 380 | 250 | 160 | |||||||
| ZHC-500 | 660 | 300 | ||||||||
| ZHC-500 | 220 | 400 | 400 | 400 | 110 | |||||
| ZHC-500 | 380 | 315 | 220 | |||||||
| ZHC-500 | 660 | 315 | 315 | 300 | ||||||
| ZHC-500 | 220 | 500 | 500 | 500 | 150 | |||||
| ZHC-500 | 380 | 400 | 280 | |||||||
| ZHC-500 | 660 | 315 | 315 | 315 | 300 | |||||
| ZHC-630 | 1000 | 690 | 220 | 800 | 630 | 630 | 630 | 630 | 200 | 630 |
| ZHC-800 | 380 | 500 | 335 | |||||||
| ZHC-1000 | 660 | 500 | 500 | 500 | 475 | |||||
| ZHC-1000 | 220 | 800 | 800 | 800 | 800 | 250 | 800 | |||
| ZHC-1000 | 380 | 630 | 450 | |||||||
| ZHC-1250 | 1250 | 660 | 500 | 500 | 500 | 475 | ||||
| ZHC-1250 | 220 | 1000 | 1000 | 1000 | 1000 | 1000 | 360 | 1000 | ||
| ZHC-1250 | 380 | 550 | ||||||||
| ZHC-1250 | 660 | 630 | 630 | 500 | 570 | |||||
| ZHC-1250 | 220 | 1250 | 1250 | 1250 | 1250 | 1250 | 375 | 1250 | ||
| ZHC-1250 | 380 | 600 | ||||||||
| ZHC-1250 | 660 | 800 | 800 | 600 | 630 | |||||
| ZHC-125/11 | 1250 | 1140 | 1140 | 125 | 125 | 40 | 40 | 40 | 55 | 125 |
| ZHC-250/11 | 250 | 1140 | 250 | 250 | 80 | 80 | 80 | 110 | 250 | |
| ZHC-500/11 | 500 | 1140 | 500 | 500 | 160 | 160 | 160 | 220 | 500 | |
| ZHC-1000/11 | 1000 | 1140 | 1000 | 1000 | - | 400 | - | 600 | 1000 | |
Frequently Asked Questions (FAQ)
Q1: Can all ZHC40 AC contactors be customized for specific requirements?
Yes, all products of the company can be customized for production according to the user's specific usage scenarios.
Q2: What are the altitude and temperature limitations for installing these contactors?
The altitude of the installation site should not exceed 2000m. The ambient air temperature should be kept between -5℃ and +40℃ for normal working conditions.
Q3: How does relative humidity affect the installation and operation?
At +40℃, relative humidity should not exceed 50%. Higher humidity is allowed at lower temperatures (e.g., up to 90% average maximum relative humidity in the wettest month with a minimum average temperature of +20℃). Proper measures must be taken to prevent condensation on the product due to temperature fluctuations.
Q4: What materials are used for the base of the ZHC40 contactors?
For ZHC40-63~125 models, the base is made of unsaturated polyester glass fiber reinforced molding compound. For ZHC40-6304 and above models, the base is constructed from aluminum alloy die-casting.
Q5: What are the installation methods and orientation limits for the contactor?
The contactor should be installed in a location free of obvious shaking, impact, and vibration. The inclination between the installation surface and the vertical plane must not exceed ±5°. ZHC40-63~125 models can be installed by screws or using a "TH75" guide rail.
Q6: What structural features improve the contactor's breaking capacity and reliability?
The ZHC40 AC contactor features an open type, direct-acting structure with double breakpoints, U-shaped iron core with a permanent air gap, and an arc extinguishing chamber made of arc-resistant plastic and an iron grid.