China ZNFO Transcender Series AC Contactor - 95A Suppliers and Factory for Reliable Motor Control Solutions
Advantage
All products of the company can be customized for production according to user usage scenarios.
Type and meaning

Note l:
- 09A-95A adopts the number of auxiliary contacts, while 115A-800A adopts the number of poles.
- 10 means three normally open main contacts and one normally open auxiliary contact (32A and below);
- 01 means three normally open main contacts and one normally closed auxiliary contact (32A and below);
- 11 means three normally open main contacts, one normally open auxiliary contact and one normally closed auxiliary contact (40A and above).
Normal working conditions and installation conditions
■
The ambient air temperature should be -5℃ ~+40℃, with the average temperature of no higher than +35℃ within 24 hours.
■
Altitude: not higher than 2000m;
■
Atmospheric conditions: when the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature, such as 90% under 20℃. Special measures should be taken for occasional condensation due to temperature change;
■
Pollution level: level 3;
■
Installation category: category III;
■
Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°;
■
Impact vibration: the product should be installed and used in a place without obvious shaking, impact and vibration.
Main parameters and technical performance
Main parameters and technical performance indicators of the contactor
| Type | ZHC-09 | ZHC-12 | ZHC-18 | ZHC-25 | ZHC-32 | ZHC-40 | ZHC-50 | ZHC-65 | ZHC-80 | ZHC-95 | ||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Rated working current | 400(380)V | AC-3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 |
| AC-4 | 3.5 | 5 | 7.7 | 8.5 | 12 | 18.5 | 24 | 28 | 37 | 44 | ||
| 690(660)V | AC-3 | 6.6 | 8.9 | 12 | 18 | 21 | 34 | 39 | 42 | 49 | 49 | |
| AC-4 | 1.5 | 2 | 3.8 | 4.4 | 7.5 | 9 | 12 | 14 | 17.3 | 21.3 | ||
| Conventional free air thermal current | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 95 | 95 | ||
| Rated insulation voltage | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | ||
| Controllable three-phase squirrel cage motor power (AC-3) kW | 230(220)V | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 | |
| 400(380)V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | ||
| 690(660)V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 37 | 37 | 45 | 45 | ||
| Operating frequency (times/h) | Electrical / mechanical endurance | AC-3 | 1200 | 1200 | 1200 | 1200 | 600 | 600 | 600 | 600 | 600 | 600 |
| AC-4 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | ||
| Mech. | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | 3600 | ||
| Electrical endurance (10,000 times) | AC-3 | 100 | 100 | 100 | 100 | 80 | 80 | 60 | 60 | 60 | 60 | |
| AC-4 | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 15 | 10 | 10 | ||
Outline and installation dimensions

Outline and installation dimensions of ZHC-09~32

Outline and installation dimensions of ZHC-40~95
| Contactor type | A max | B max | C max | D max | E max | a | b | φ |
|---|---|---|---|---|---|---|---|---|
| ZHC-09~12 | 47 | 76 | 82 | 120.5 | 140.5 | 34/35 | 56/60 | 4.5 |
| ZHC-18 | 47 | 76 | 87 | 125.5 | 145.5 | 34/35 | 50/60 | 4.5 |
| ZHC-25 | 57 | 86 | 95 | 133.5 | 153.5 | 40 | 48 | 4.5 |
| ZHC-32 | 57 | 86 | 100 | 138.5 | 158.5 | 40 | 48 | 4.5 |
| ZHC-4011~6511 | 77 | 129 | 116 | 154.5 | 174.5 | 40 | 105 | 6.5 |
| ZHC-4004~6504 | 84 | 129 | 116 | 154.5 | 174.5 | 40 | 105 | 6.5 |
| ZHC-4008~6508 | 84 | 129 | 127 | 154.5 | 174.5 | 40 | 105 | 6.5 |
| ZHC-8011~9511 | 87 | 129 | 127 | 165.5 | 185.5 | 40 | 105 | 6.5 |
| ZHC-8004~9504 | 96 | 129 | 122 | 160.5 | 180.5 | 40 | 105 | 6.5 |
| ZHC-8008~9508 | 96 | 129 | 135 | 160.5 | 180.5 | 40 | 105 | 6.5 |
Frequently Asked Questions (FAQ)
Can ZHC contactors be customized for specific applications?
Yes, all products can be customized for production according to the user's specific usage scenarios and requirements.
What do the auxiliary contact numbers 10, 01, and 11 mean?
"10" means three normally open main contacts and one normally open auxiliary contact (32A and below); "01" means three normally open main contacts and one normally closed auxiliary contact (32A and below); "11" means three normally open main contacts, one normally open auxiliary contact, and one normally closed auxiliary contact (40A and above).
What are the ambient air temperature and altitude limits for installation?
The ambient air temperature must be between -5℃ and +40℃ (with a 24-hour average not exceeding +35℃). The installation altitude should not exceed 2000 meters.
What are the relative humidity requirements for the operation environment?
At the maximum temperature of +40℃, the relative humidity should not exceed 50%. Higher relative humidity is permitted at lower temperatures (e.g., up to 90% at 20℃). Special precautions should be taken to prevent condensation.
What is the maximum allowed installation inclination for the contactor?
The inclination between the contactor's installation surface and the vertical plane must not exceed ±5° to ensure proper operation.
What is the rated insulation voltage of the ZHC contactor series?
All ZHC contactor models, from ZHC-09 up to ZHC-95, have a rated insulation voltage of 690V.