China ZNFO Transcender Series AC Contactors - Reliable Suppliers & Factory for 50Hz/60Hz Applications

The ZHC series AC contactor is an essential component for electrical circuits operating at 50Hz or 60Hz frequencies, capable of handling voltages up to 690V and rated currents up to 95A. Primarily designed for use in categories AC-3 and 400(380)V, these contactors are ideal for remotely connecting and disconnecting circuits, starting and controlling AC motors frequently, and providing protection against overloads when used alongside appropriate thermal relays to form electromagnetic starters, Our contactors strictly adhere to international standards, including GB/T-14048.4-2020 and IEC 60947-1 (1999), IEC 947-4-1, ensuring reliability and safety in your electrical applications. As a trusted manufacturer and supplier in China, we are committed to delivering high-quality products from our factory to meet your electrical needs

    Advantage

    All products of the company can be customized for production according to user usage scenarios.

    Type and meaning

    Type and meaning chart
    Note l

    09A-95A adopts the number of auxiliary contacts, while 115A-800A adopts the number of poles.

    10 means three normally open main contacts and one normally open auxiliary contact (32A and below);

    01 means three normally open main contacts and one normally closed auxiliary contact (32A and below);

    11 means three normally open main contacts, one normally open auxiliary contact and one normally closed auxiliary contact (40A and above).

    Normal working conditions and installation conditions

    • The ambient air temperature should be -5℃ ~+40℃, with the average temperature of no higher than +35℃ within 24 hours.
    • Altitude: not higher than 2000m;
    • Atmospheric conditions: when the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature, such as 90% under 20℃. Special measures should be taken for occasional condensation due to temperature change;
    • Pollution level: level 3;
    • Installation category: category III;
    • Installation condition: the inclination between the installation surface and the vertical plane should not exceed ±5°;
    • Impact vibration: the product should be installed and used in a place without obvious shaking, impact and vibration.

    Main parameters and technical performance

    Main parameters and technical performance indicators of the contactor
    Type ZHC-09 ZHC-12 ZHC-18 ZHC-25 ZHC-32 ZHC-40 ZHC-50 ZHC-65 ZHC-80 ZHC-95
    Rated working current 400(380)V AC-3 9 12 18 25 32 40 50 65 80 95
    AC-4 3.5 5 7.7 8.5 12 18.5 24 28 37 44
    690(660)V AC-3 6.6 8.9 12 18 21 34 39 42 49 49
    AC-4 1.5 2 3.8 4.4 7.5 9 12 14 17.3 21.3
    Conventional free air thermal current 20 20 32 40 50 60 80 80 95 95
    Rated insulation voltage 690 690 690 690 690 690 690 690 690 690
    Controllable three-phase squirrel cage motor power (AC-3) kW 230(220)V 2.2 3 4 5.5 7.5 11 15 18.5 22 25
    400(380)V 4 5.5 7.5 11 15 18.5 22 30 37 45
    690(660)V 5.5 7.5 10 15 18.5 30 37 37 45 45
    Operating frequency (times/h) Electrical/mechanical endurance AC-3 1200 1200 1200 1200 600 600 600 600 600 600
    AC-4 300 300 300 300 300 300 300 300 300 300
    Mechanical 3600 3600 3600 3600 3600 3600 3600 3600 3600 3600
    Electrical endurance (10,000 times) AC-3 100 100 100 100 80 80 60 60 60 60
    AC-4 20 20 20 20 20 15 15 15 10 10

    Outline and installation dimensions

    Dimensions of ZHC-09~32
    Outline and installation dimensions of ZHC-09~32
    Dimensions of ZHC-40~95
    Outline and installation dimensions of ZHC-40~95
    Contactor type A max B max C max D max E max a b φ
    ZHC-09~12 47 76 82 120.5 140.5 34/35 56/60 4.5
    ZHC-18 47 76 87 125.5 145.5 34/35 50/60 4.5
    ZHC-25 57 86 95 133.5 153.5 40 48 4.5
    ZHC-32 57 86 100 138.5 158.5 40 48 4.5
    ZHC-4011~6511 77 129 116 154.5 174.5 40 105 6.5
    ZHC-4004~6504 84 129 116 154.5 174.5 40 105 6.5
    ZHC-4008~6508 84 129 127 154.5 174.5 40 105 6.5
    ZHC-8011~9511 87 129 127 165.5 185.5 40 105 6.5
    ZHC-8004~9504 96 129 122 160.5 180.5 40 105 6.5
    ZHC-8008~9508 96 129 135 160.5 180.5 40 105 6.5

    Frequently Asked Questions (FAQ)

    Can these contactors be customized for specific applications?
    Yes, all products of the company can be customized for production according to the user's specific usage scenarios.
    What are the ambient temperature requirements for installation?
    The ambient air temperature should be within the range of -5℃ to +40℃, and the average temperature over a 24-hour period must not exceed +35℃.
    What is the maximum altitude limit for normal operating conditions?
    The contactors should be installed at an altitude not higher than 2000 meters above sea level.
    What do the auxiliary contact codes "10" and "01" stand for?
    For models 32A and below: "10" means three normally open main contacts and one normally open auxiliary contact; "01" means three normally open main contacts and one normally closed auxiliary contact.
    What is the maximum allowable installation inclination?
    The inclination between the installation surface and the vertical plane should not exceed ±5° during installation.
    Can the contactor be installed in environments with high vibration?
    No, the product should be installed and used in locations that are free from obvious shaking, impact, and vibration.