CJ19 Capacitor Changeover Contactor from China Factory - Reliable Suppliers for Low-Voltage Reactive Power Control

The CJ19 series capacitor changeover contactor, commonly referred to as the contactor, is a high-quality electrical component designed specifically for power circuits operating at frequencies of AC 50Hz or 60Hz, with a maximum rated working voltage of 400V. This reliable product is essential for efficiently activating or deactivating low-voltage reactive power compensation equipment and shunt capacitors, Manufactured in China, our contactors are equipped with advanced inrush current suppression devices, effectively minimizing the adverse effects of closing inrush currents on capacitors and preventing overvoltage during the disconnection process. As trusted suppliers in the industry, our factory ensures that each unit meets stringent quality standards, making the CJ19 series an ideal choice for your electrical needs

    Type and meaning

    CJ19 series capacitor changeover contactor
    Notes:
    1. The number of auxiliary contacts is represented by two digits, of which the tens digit is the logarithm of normally open contacts, and the units digit is the logarithm of normally closed contacts.
    2. For AC-6b 400vAT, the rated working currents corresponding to various specification codes are 25(18A), 32(24A), 43(29), 50(36A), 63(48A), 95(58A), 125(87A).

    Normal working conditions and installation conditions

    The ambient air temperature should not exceed +40℃, with the average temperature of no higher than +35℃ within 24 hours. The lower limit of the ambient air temperature should be -5℃: When the highest temperature is +40℃, the relative humidity of the air should not be higher than 50%; A higher relative humidity is allowed at a lower temperature.
    The altitude of the installation site should not exceed 2000m.
    Pollution level: level 3.
    Installation category: category II.
    Installation condition: the inclination between the installation surface of the contactor and the vertical plane should not exceed 5°.
    Impact and vibration: the product should be installed in a place without obvious shaking, impact and vibration.

    Schematic diagram of wiring

    For the schematic diagram of wiring of CJ19 series, please refer to Fig. 1.
    CJ19 series capacitor changeover contactor 02

    L1~L3 should be connected to the power supply side; T1~T3 should be connected to the load side.

    Main parameters and technical performance

    CJ19 25 32 43 63 95 115 150 170
    Rated insulation voltage(Ui)V 500V 690V
    Rated working voltage(Ue)V 220V/240V、380V/400V
    Controllable capacitor Capacity(Qn)Kva 220V 6 9 10 15 28.8(240V) 34.5(240V) 46(240V) 52(240V)
    380V 12 18 20 30 50(400V) 60(400V) 80(400V) 90(400V)
    Conventional free air thermal current Ith 25 32 43 63 63 200 200 275
    Rated working current(AC-6b)le A 17 23 29 43 43 87 115 130
    Inrush current suppression capability 20le
    Control power supply voltage UsV 110、127、220、380
    Auxiliary contact AC-15:360VA DC-13:33W Ith:10A
    Operating frequency times/h 120
    Electrical endurance 10,000 times 10 2
    Mechanical endurance 10,000 times 100 300
    Dimensions and type Outline dimensions Installation dimensions
    A B C D A B φ Calliper gauge
    CJ19-25 76 47 125 120 35 50/60 4.5 35
    CJ19-32 86 58 135 130 40 50/60
    CJ19-43 86 58 135 130 40 50/60
    CJ19-63 128 79 156 150 40 100/110 6.5 35/75
    CJ19-80 128 160 200 200 40 100/110
    CJ19-95 128 160 200 200 40 100/110

    Shape and installation dimensions(mm)

    CJ19 series capacitor changeover contactor 03

    Fig.2 Diagram of outline and installation dimensions of CJ19-25,32,43

    Frequently Asked Questions (FAQ)

    Q What are the ambient temperature requirements for the CJ19 series contactor?

    The ambient air temperature should not exceed +40℃, with the average temperature of no higher than +35℃ within 24 hours. The lower limit of the ambient air temperature is -5℃.

    Q What is the maximum installation altitude for the CJ19 contactor?

    The altitude of the installation site should not exceed 2000 meters.

    Q How should the power supply and load sides be wired?

    According to the wiring schematic diagram, L1~L3 should be connected to the power supply side, and T1~T3 should be connected to the load side.

    Q What is the inrush current suppression capability of the CJ19 contactor?

    The inrush current suppression capability of the CJ19 series contactor is rated at 20Ie.

    Q What are the pollution level and installation category ratings?

    The CJ19 series contactor is rated under pollution level 3 and installation category II.

    Q What is the maximum allowed installation inclination for the contactor?

    The inclination between the installation surface of the contactor and the vertical plane should not exceed 5°.