Direct-acting AC Contactor CJX2F from China Suppliers and Factory - Up to 1400A, 1000V for Power Systems
Type and meaning
Structural features of the product
It has simple, compact, new and unique structure, with formular function and assembly modularization.
The coil is packaged in plastic, with advanced technology, beautiful appearance, good insulation strength and high mechanical strength.
For CIX2-F115-780-1200-1400,coil and static iron core form a drawer for pushing in and pulling out by pressing the but on and thus for easy repair.
The arc extinguishing chamber is made of high-strength plastic, which has high mechanical strength and good arc extinguishing performance, and is fixed by locking bar rotating compression spring, which is convenient and reliable.
There are many auxiliary contacts, which are replaced easily, For CIX2-F115-780~1200~1400 contactors, the coil is provided with a special auxiliary contact for DC control of self-locking conversion. It is allowed to additionally install two auxiliary contactor sets so that there are 8 pairs of auxiliary contactors. The auxiliary contactor sets are installed only along the guide rail, with no need of screws. Give it a push, when you hear a click, the auxiliary contactor sets are installed successfully.If the air damping type time relay is required, it can be used directly to replace the auxiliary contact set.
The contactor can save electricity significantly.CJX2-F400-780~1200-1400 features AC input and DC control.
The mechanical interlocking of the contactor is simple and reliable.Two contactors can be interlocked horizontally, ClX2-F115-630 contactors can also realize vertical interlocking of two contactors and vertical interlocking between three contactors.
Main parameters and technical performance
Action performance:the pull in voltage is 85%~110% Us;the release voltage is 20% ~75% Us for AC coils and 10% ~75% Us for DC coils.
Control voltage of coils:AC 127,220,380V and DC 110, 220V for CJX2F-115~780~1400;Coils of any other voltage are also supported.
NT series fuses are recommended as the suitable short-circuit protection appliances of the contactor.
For technical parameters of contactor,please refer to the table below.
| Type | CJX2-F115 | CX2-F150 | CJX2-F185 | CX2-F225 | CJX2-F265 | CJX2-F330 | CJX2-F400 | CJX2-F500 | CJX2-F630 | CJX2-F780 | |||||
| Rated insulation voltage | 1000 | ||||||||||
| Conventional thermal current | 200 | 250 | 275 | 315 | 350 | 400 | 500 | 700 | 1000 | 1500 | |
| Working current under the use category of AC-3 | 380V | 115 | 150 | 185 | 225 | 265 | 330 | 400 | 500 | 335 | 780 |
| 660V | 65 | 80 | 95 | 115 | 150 | 185 | 225 | 265 | 225 | 450 | |
| 1000V | 40 | 50 | 65 | 80 | 95 | 115 | 150 | 185 | 320 | 300 | |
| Control motor power under the use category of AC-3 | 380V | 55 | 75 | 90 | 110 | 132 | 165 | 200 | 250 | 335 | 400 |
| 660V | 80 | 110 | 110 | 129 | 160 | 220 | 280 | 335 | 450 | 475 | |
| 1000V | 65 | 65 | 100 | 100 | 147 | 160 | 185 | 335 | 425 | 450 | |
Outline and installation dimensions
Notes: 1) M is the flash over distance; 2) F is the space required for replacement of coils.

Outline dimensions of CJX2-F400~500 Fig.3

Outline and installation dimensions of CJX2-F630 Fig.4
| Type | Number of poles | A | B | C | DG | E | F2) | Gb1 | HN | M) | P | S | B1M | Mounting screw |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CJX2-F115 | 3 poles | 163.5 | 162 | 171 | 80 | 113 | 131 | 137 | 124 | 40 | 37 | 20 | 147 | M6 |
| 4 poles | 200.5 | 162 | 171 | 80 | 113 | 131 | 137 | 124 | 40 | 37 | 20 | 147 | M6 | |
| CJX2-F150 | 3 poles | 163.5 | 172 | 171 | 80 | 113 | 131 | 137 | 124 | 40 | 40 | 20 | 150 | M6 |
| 4 poles | 200.5 | 172 | 171 | 80 | 113 | 131 | 137 | 124 | 40 | 40 | 20 | 150 | M6 | |
| CJX2-F185 | 3 poles | 168.5 | 174 | 181 | 80 | 113 | 131 | 137 | 127 | 40 | 40 | 20 | 154 | M6 |
| 4 poles | 208.5 | 174 | 181 | 80 | 113 | 131 | 137 | 127 | 40 | 40 | 20 | 154 | M6 | |
| CJX2-F225 | 3 poles | 168.5 | 197 | 181 | 80 | 113 | 131 | 137 | 127 | 50 | 48 | 25 | 172 | M6 |
| 4 poles | 208.5 | 197 | 181 | 80 | 113 | 131 | 137 | 127 | 50 | 48 | 25 | 172 | M6 | |
| CJX2-F265 | 3 poles | 201.5 | 203 | 213 | 96 | 113 | 147 | 145 | 147 | 50 | 48 | 25 | 178 | M6 |
| 4 poles | 224.5 | 203 | 213 | 96 | 113 | 147 | 145 | 147 | 50 | 48 | 25 | 178 | M6 | |
| CJX2-F330 | 3 poles | 213 | 206 | 219 | 96 | 113 | 147 | 145 | 158 | 60 | 48 | 25 | 181 | M6 |
| 4 poles | 261 | 209 | 219 | 96 | 113 | 147 | 145 | 158 | 60 | 48 | 25 | 181 | M6 | |
| CJX2-F400 | 3 poles | 213 | 209 | 219 | 80 | 175 | 119 | 209 | 158 | 60 | 48 | 25 | 181 | M8 |
| 4 poles | 261 | 209 | 219 | 80 | 175 | 119 | 209 | 158 | 60 | 48 | 25 | 181 | M8 | |
| CJX2-F500 | 3 poles | 233 | 238 | 232 | 80 | 175 | 141 | 209 | 158 | 70 | 55 | 30 | 208 | M8 |
| 4 poles | 288 | 238 | 232 | 140 | 175 | 141 | 209 | 158 | 70 | 55 | 30 | 208 | M8 | |
| CX2-F630 | 3 poles | 309 | 304 | 255 | 180 | 185 | 181 | 280 | 202 | 80 | 40 | 40 | 264 | M10 |
| 4 poles | 389 | 304 | 255 | 240 | 185 | 181 | 280 | 202 | 80 | 40 | 40 | 264 | M10 |
Frequently Asked Questions
What are the coil control voltage options for the CJX2F contactor series?
The standard control voltages for CJX2F-115~780~1400 contactors are AC 127V, 220V, 380V and DC 110V, 220V. Coils of any other voltage can also be supported upon request.
How easy is it to replace or repair the coil on CJX2-F115-780-1200-1400 models?
Repair is very convenient because the coil and the static iron core form a drawer structure. You can easily push it in and pull it out simply by pressing the button.
What is the recommended short-circuit protection for these AC contactors?
NT series fuses are recommended as the suitable short-circuit protection appliances for these contactors to ensure safe and reliable operation.
Can these contactors be interlocked mechanically?
Yes. Two contactors can be interlocked horizontally. For CJX2-F115-630 contactors, you can also achieve vertical interlocking of two contactors and vertical interlocking among three contactors.
How are the auxiliary contactor sets installed?
The auxiliary contactor sets are installed easily along the guide rail without any screws. Simply give it a push, and when you hear a click, they are successfully installed.
What are the pull-in and release voltage parameters?
The pull-in voltage is 85% to 110% Us. The release voltage is 20% to 75% Us for AC coils and 10% to 75% Us for DC coils.